Xeyr ad vahid Parametr
1 Nominal gərginlik kV 24
2 İzolyasiya səviyyəsi 1min power frequency withstand voltage kV 65 (79)
Lightning impulse withstand voltage kV 125 (145)
3 Rated tezlik Hz 50
4 Main bus rated current A 630, 1250, 1600 2000, 2500 2500, 3150, 4000
5 Qiymətləndirilmiş qısamüddətli cərəyan kA 16, 20, 25 25, 31.5 31.5, 40, 50
6 Qiymətli zirvə cərəyana tab gətirir kA 40, 50, 63 63, 80 80, 100, 125
7 Sürət məsafəsi mm/kV 20
8 Müdafiə səviyyəsi
IP4X (IP2X after the cabinet door is opened)
9 çəki kg 900

8aZr_O95QTCxr3jhyGdOYQ

Xüsusiyyətləri

● The cabinet body is assembled by multiple bending of aluminum-zinc plate, which avoids the error caused by welding, and the processing and assembly accuracy of the cabinet body is high.

● Adopt a center-mounted layout, mechanical stability and good interchangeability.

● Using D-type or O-type busbars, and epoxy resin vulcanization process, to achieve full insulation, improve the distribution of the electric field in the cabinet, and improve the overall insulation level of the switchgear.

● The device is equipped with a variety of blocking functions: such as the electric entry and exit of the circuit breaker trolley, the electric opening and closing operation of the ground switch, etc., which can prevent the operator from entering the live interval by mistake.

● The entry and exit operation of the circuit breaker trolley, the opening and closing operation of the grounding switch, and the opening and closing operation of the circuit breaker can all be electrically operated. And the PLC is used to measure and control the operation procedures of the on-off operation to realize the programmed operation. Use the touch screen as the man-machine interface, and operate the corresponding parts on the simulation diagram provided by the touch screen.


Xüsusi tətbiqetmələr

Note: Anything beyond the scope of the above requirements shall be determined by the user in consultation with the manufacturer. For special places, such as underground substations, unattended substations and other poor operating conditions, constant temperature cooling equipment should be added indoors to improve product operating conditions and ensure safe and reliable operation of the equipment.